Questions & Answers on Power Transformers

   

1-What do you mean by power transformer?

It is a static Electro-magnetic machine which transforms alternating current from one AC voltage to another AC voltage at same frequency & at the same apparent power (KVA).

2-What is the principle of Power transformer operation?

Power transformers work on the principle of electromagnetic induction. Which states that, EMF induced in a closed conducting circuit when the magnetic flux linking with that circuit changes in time.

3-What is the main function of a power transformer?

Generally it is used for stepping up or stepping down of Voltage to desired level

4-What are the various parts of power transformer?

General arrangement of Power Transformer


  • Casing
  • Core
  • Primary & secondary windings
  • LV & HV bushings
  • Radiators & cooling system
  • Conservator
  • Breather
  • Protection devices like Buchholz relay, relief valves, temperature sensors

5-Why does the oil conservator is placed at higher elevation?

Oil conservator is placed at a slightly higher level than that of the tank. It accommodates the contraction & expansion of oil level during lower & higher loads respectively. At higher load, oil temperature rises and hence level in the conservator rises & at lower load, oil temperature decreases & level in conservator drops down.

The above cushioning in oil level is by cushioning bag present in conservator, the air cushion in the conservator permits expansion & contraction of the oil tank without contact with moist air.

6-What is the function of breather in Transformers?

Breather is installed in a pipe from conservator. One end is connected to air cushion bag in the conservator, other end is connected to external air.

Breather is filled with dry silica jel, generally pink in colour. When oil in the conservator rises, air is let out through the breather. During low load when oil level in the conservator decreases, air is sucked into the cushion bag through breather. Silica jet absorbs the moisture & lets only dry air. Wet silica jells are blue in color.

7-What is the function of Buchholzs relay?



It is fitted in the pipe between conservator tank & main oil tank. It operates by gas during arcing or short circuits

8-What are the various cooling methods employed in Power transformers?

  • ONAN: Oil Natural & Air Natural
  • ONAF: Oil natural & Air forced
  • OFAF: Oil forced & Air forced
  • OFWF: Oil forced & water forced
  • AN: Air natural

9-What is the function of Pressure relief valve in Transformers?

It is fitted on tank to vent out the gases formed in oil & hence protects the transformer from explosion

10-What do you mean by small, medium & large transformers?

  • Small transformers: < 5 KVA
  • Medium transformers: 5 to 500 KVA
  • Large transformers :> 1 MVA

11-What do you mean by core type transformer?

In this type of transformers, winding surround the limbs of core

12-What do you mean by the Shell type transformer?

In this type of transformers, core surrounds the major portion of the windings

13-What is the relation between voltage, current and number of turns on coils in a transformer?

We have following relation:

Vp/Vs = Np/Ns = Is/Ip

Where, Vp and Vs are Voltage on primary and secondary side.

Np and Ns are No. of turns on primary and secondary coils.

IP and Is are Primary side current and secondary side current of a transformer.

14-A 10 KVA single phase 2200/220 Volts Transformer has 60 turns on secondary side, then calculate Primary current, no. of turns on coil and secondary side current.

Given that,

Vp = 2200 V

Vs 200 V

Ns 60

Transformer rating 10 KVA

We know that Vp/Vs = Np/Ns

Np 60 X 2200/220 = 600 turns

Further, KVA rating of transformer is (Vp Ip)/1000 and (Vs X Is)/1000

10 2200 Ip/1000

Therefore, current on primary side Ip 10 X 1000/2200 = 4.54 Amps

Similarly current on secondary side Is 10 1000/220 45.45 Amps

15-A Power transformer’s input voltage is 11 KV & output voltage is 110 KV,then calculate the number of turns on secondary side, if Primary side winding has 25 turns

We have

V1 / V2 = N1 / N2

11 / 110 = 25 / N2

N2 = 250 Nos

16-A power transformer input voltage is 11 KV & output voltage is 220 KV, then calculate the secondary side current if it has 2300 Amps of current on primary side?

We have

V1 / V2 = I2 / I1

11 / 220 = I2 / 2300

I2 = 115 Amps

17-What are the materials of composition of lamination cores?

Laminations are thin 0.2 to 0.3mm thick silicon sheets. These are further coated by varnish or insulation oxide.

18-Why do the laminations are made up of silicon steel sheets?

Higher the silicon content in steel sheets increases the resistivity & reduces the eddy current losses. But silicon percentage is restricted up to 3.25% max.to avoid brittleness of sheet.

19-What are the various tests carried out on Transformers?

Meggering

  • IR value measurement
  • Magnetic balance test
  • Magnetizing current test
  • Capacitor measurement
  • Ratio test
  • Vector group test
  • Induced voltage test
  • Temperature rise test
  • BDV test
  • No load current test
  • No load loss test

20-What is the significance of magnetizing current test?

  • This test is performed to locate the defects in the magnetic core structure,
  • To detect the shifting of winding, failure
  • To detect the problems in tap changers

21-What are factors which affect IR value of transformer?

  • Surface condition of the terminal bushings
  • Quality of oil
  • Quality of winding insulation
  • Temperature of oil
  • Duration of application & value of test voltage

22-What are the various protections given for power transformers?

  • Differential protection for earth faults
  • High oil temperature & high winding temperature protection
  • Over current protection
  • Over fluxing protection
  • Protection against fire
  • Protection against lightening
  • Buchholz relay for gas & arcing protection
  • Pressure relief valve

23-On what factors transformer loading depends on?

  • Transformer current
  • Winding temperature
  • Oil temperature

24-What are the effects of Transformer over loading?

Overloading results into

  • Cellulose insulation becomes mechanically weak & resulting in winding failure
  • Oil gets rapidly oxidized

25-What is the function of tap changer in Power transformers?

Tap changer is for adjusting the secondary voltage

26-What do you mean by No-load current?

The current flowing through the terminal of a winding when rated voltage is applied at rated frequency the other winding being left open circuited

27-What do you mean by no-load losses in Power transformers?

The active power absorbed when rated voltage at rated frequency is applied to the terminals of one winding, with other winding being left open circuited

28-What parameters of Transformer oil are tested yearly?

Transformer oil qualities are recommended as per IS-335-1963

  • Density
  • Kinematic Viscosity
  • Flash Point
  • Pour point
  • Neutralization Number (Acidity)
  • Sludge
  • Moisture content
  • Dissolved Gas Analysis (DGA)
  • Dielectric Dissipation test
  • Interfacial tension
  • Break down Voltage

29-What is the importance of Transformer BDV test?

BDV test is done to detect moisture, dirt & conductive particles in the oil. The BDV value should be more than 50 KV

30-Briefly explain the BDV test of transformer oil?

This test applies an AC voltage of frequency 40 to 60 Hz through two polished electrodes having diameter 12.5mm to 13 mm with oil gap around 2.5 to 4.0 mm.Rise in voltage between the electrodes is at uniform rate of 2 KV/sec.Thus voltage is increased from zero to till breakdown.

The final value will be arithmetic mean of 6 consecutive tests

 

 

It's all about HP heaters (Feed water heaters) in Power plants

 1-Why do you use HP heaters in power plants?

HP heaters are used for heating the feed water, which will contribute in increasing cycle efficiency as well as reduction in fuel consumption

2-What is the design code of HP heaters?

HEI, ASME SEC VIII Div-I IBR

3-What are the advantages of using feed water heaters in power plants?

  • Fuel consumption reduces
  •  Reduce heat losses in the condenser
  •  Lower emissions as fuel use is reduced due to improved heat rate
  • Decreases the plant heat rate & hence increases the plant efficiency

4-What are the different types of feed water heaters?

Open type feed water heaters & closed type feed water heaters

5-What do you mean by open type of feed water heaters?

In open type feed water heaters steam directly mixes with feed water. Steam pressure used is lower < 5 kg/cm2

6-What do you mean by closed type of feed water heaters?

In closed type feed water heaters steam directly mixes with feed water. Steam pressure used is high > 5 kg/cm2, these are shell & tube type heat exchangers

7-What are the pipe lines connected to HP heaters?

  • Bleed steam inlet line
  • Feed water inlet line
  • Condensate outlet line
  • Feed water outlet line
  • Feed water box drain & vent lines
  • Shell zone drain & vent

8-What are the MOCs of Tubes & shells used in closed type of HP heaters?

Tubes: SA 213 TP 304 (Feed water pressure up to 170 kg/cm2)

Shell: SA 516 Gr.70

9-What are the different zones of HP heaters?

















  • Desuper heating zone
  • Condensing zone
  • Sub cooling zone

10-Where does the maximum heat transfer occur out of all zones?

Maximum heat transfer occurs at condensing zones

11-Why the name Sub-cooling has come?

Here condensed steam from condensing zone is cooled by feed water entering by convective heat transfer method.

12-What is the function of drain coolers in HP heaters?

Drain Coolers are employed because of heat consumption improvement in case of drain introduction into the lower heater through the control valve.

13-Why the feed water inlet line connection is at the bottom & outlet line is at the top?

          

Feed water inlet line & outlet line are connected in such a way that to separate desuperheating zone, condensing zones & sub cooling (drain cooler) zones

14-Where do the fixed & sliding supports of HP heaters are located?















Fixed support: Towards feed water inlet & outlet line

Sliding support: Opposite side of feed water line connections

15-What would be the velocity of feed water in HP heaters tubes?

It’s around 0.6 to 0.8 m/sec

16-What is the effect of high/low condensate level in heaters shell?

Higher the condensate level lower is the performance of heater and vice versa. Heater level is always maintained in between 30–50%.

17-Briefly explain the condensate level control in HP heaters?

One of the most common causes of tube failures in a feed water heater (FWH) is the improper control of the internal liquid level, which also can cause operational and maintenance costs that might lead to premature replacement. These problems are not new, they have been experienced by many utility plants throughout the industry during the past 50 years. However in many cases, the resulting damaging phenomenon has seldom been totally understood and the loss of corporate knowledge and failure of some utilities to identify and rectify level control problems continues to bring this issue to the forefront of root causes of FWH operational failures.

In general, the performance of the Drain Cooler (DC) Zone is tied to the operational parameter of Drain Cooler Approach (DCA). DCA is a good indication of whether the DC Zone is operating properly or not, it is not the only parameter that should be considered. DCA is a measurement of temperatures

The pressure of the drains also must be known in order to determine the degree of sub cooling and whether there is a potential for flashing, either within the DC itself or the downstream piping before the level control valve. Flashing and two-phase flow in either of these areas can cause significant damage to the heater.

It is important to remember that the drain cooler is designed to be a water-to-water exchanger. It must remain that way to function properly. Any admission of vapour into the zone typically results in problems. This might be a result of a low liquid level in which steam is admitted directly from the condensing zone into the DC zone, the result of flashing within the DC zone itself, or can be the result of leakage into the zone via the endplate or shroud cracks.

18-What do you mean by drain cooler approach (DCA) in HP heaters?

DCA is the temperature difference between the drains (steam condensate) leaving the heater and the temperature of feed water entering the heater. For more cycle efficiency DCA value should be small.

19-A HP heater is used to heat the feed water from 160 °C to 180 °C by using turbine bleed steam at 15 kg/cm2 and 320 °C. The condensate returning from heater is at 170 °C, calculate the DCA of heater.
















We have,

DCA = Temperature of condensate leaving the heater – Temperature of feed water entering the heater

DCA = 170 - 160 = 10 °C

Note: For best performance, heaters are designed to get DCA 3 to 5 °C at full operation capacity.

20-What do you understand by Terminal Temperature Difference (TTD)?

It is the difference between the saturation temperature at the operating pressure of the inlet steam to the heater and the temperature of the feed water leaving the heater. For more cycle efficiency TTD value should be small.

21-A HP heater is used to heat the feed water from 110 °C to 160 °C by using MP steam at pressure 13 kg/cm2 at temperature 280 °C, calculate the TTD.







We have,

TTD = Saturation temperature of inlet steam - Feed water outlet temperature

Saturation temperature of inlet steam at 13 kg/cm2g pressure = 195.6 °C

TTD = 195.6 - 160 = 35.6 °C

Note: For best performance, heaters are designed to get TTD 3 to 5 °C at full operation capacity.

22-How the DCA does affects condensate level of HP heaters?

An increase in DCA,HP heater level decreases & vice versa

23-What is flashing in heaters? How does it occur?

Flashing, by definition, is the change in state of liquid to vapour. While in most cases this change of state results from the addition of heat (as in the boiler) in a FWH the most common cause of flashing is a result of a reduction in pressure (or pressure drop). Pressure drop might be a result of the geometry of the Drain Cooler Entrance window, the fact that the drains must travel around the tubes and change direction many times due to the baffling arrangement and also due to changes in elevation and elbows in the downstream piping. If the liquid drains are not sub cooled enough, any one of these pressure drops could result in flashing and two-phase flow. Two-phase flow is known to cause problems to piping, tubing, the cage and the shell, especially in the case of carbon steel components.

24-What do you mean by fouling in heat exchangers?

Deposition of any undesired material on heat transfer surfaces is called fouling. Fouling may significantly impact the thermal and mechanical performance of heat exchangers. Fouling is a dynamic phenomenon which changes with time. Fouling increases the overall thermal resistance and lowers the overall heat transfer coefficient of heat exchangers. Fouling also impedes fluid flow, accelerates corrosion and increases pressure drop across heat exchangers.

Different types of fouling mechanisms have been identified. They can occur individually but often occur simultaneously.

Scaling:

  • Particulate/Sedimentation Fouling
  • Corrosion Fouling
  • Chemical Fouling
  • Freezing Fouling

25-What are the problems associated with HP heaters?

  •  Initial two phase mixture & hammering
  • Tubes failure due to wrong operation
  • Level fluctuation & leakages
  • Overfeeding of steam & feed water
  • Operating the heaters above the operating & design parameters

26-Write down the initial charging process of feed water heater (HP heater)

Steps:

  • Ensure all the maintenance activities on HP heaters are completed
  • Ensure all inlet & outlet valves of heaters are healthy
  • Ensure all field instruments are healthy
  • Keep open all water box & shell side vents & drains are  open
  • Ensure steam condensate outlet valve is open

Water side

  • Crack Open the feed water outlet valve
  • Then crack open the feed water inlet valve
  • Allow to vent out the air
  • Then gradually open the outlet & inlet feed water valves
  • Then close the water box vents & drain valves

Steam side

  • Ensure steam line drains are in opened condition
  • Ensure steam parameters are as per desired values
  • Ensure no water in steam line drains
  • Crack open the steam inlet valve to HP heater
  • Ensure there are no water particles in drain & vent line of shell. If found clear, then close the valves
  • Then gradually open steam inlet valves & allow for stabilization

27-A HP heater is used to heat the 200 TPH feed water from 160 °C to 180 °C by using turbine bleed steam at 15 kg/cm2 and 320 °C. The condensate returning from heater is at 170 °C, calculate the quantity of steam used.

 Given that,

Qf = 200 TPH

Tf1 = 160 °C

Tf2 = 180 °C

Hg  at pressure 15 kg/cm2 & temperature 320 °C =735.3 kcal/kg

Enthalpy of condensate water Hf = 171 kcal/kg

Heat lost by the steam = Heat gained by feed water

Ms X (Hg-Hf) = Mw X (Tf2-Tf1)

Ms X (735.3-171) = 200 X (180-160)

Ms = 7.08 TPH

28-What are the precautions to be taken for safe operation of HP heaters?

Precautions:

  • Operate the HP heaters as per SOP
  • Take utmost care during initial charging
  • Do not operate the heaters beyond the operating pressure & temperature
  • Bypass the HP heaters during Boilers Hydraulic tests
  • Conduct routine preventive maintenance




Zebronics Zeb-County Bluetooth Speaker with Built-in FM Radio, Aux Input and Call Function (Black)

                                          


Various IBR forms, acts & regulations for a power plant engineers

Sl No.
IBR Form No.
Details of forms
1
I
Memorandum for Boiler inspection or registration
2
II
Issued by inspection authority during new construction
3
II A
Issued by inspection authority during new construction for foreign code boilers
4
III
Certificate of manufacture issued by constructor
5
III A
Steam pipe line test certificate  issued by manufacturer
6
III B
Tubes  test certificate issued by manufacturer
7
III C
Test certificates for  fittings & mountings (Valves,bend,elbow,tee etc)
8
III F
Test certificates of casting & forging issued by manufacturer
9
V
Boiler use provisional order issued by Boiler inspector authority
10
VI
Certificate issued by  directorate of steam boiler for boiler use
11
VII
Inspecting authority (directorate of steam boiler) certificate for constructional Boiler
12
XI
Certificate for the use of an Economiser
14
XII
Welder qualification record
15
XIII
IBR welder certificate
16
XVI-F
Certificate for approval of tube maker
17
XVI-G
Certificate for approval of pipe maker
18
XVI-H
Certificate for approval of material testing laboratory
19
XV-I
Certificate for approval for RLA organisation
20
Form No.C
Certificate for 2nd class Boiler attendant issued by Directorate of steam Boilers under rule-41
21
Form No.B
Certificate for 1st class Boiler attendant issued by Directorate of steam Boilers under rule-41
22
Form No.B
Certificate for BOE  issued by Directorate of steam Boilers under rule-40 Boiler operation engineer-2011

Power plant consruction materials & welding electrodes used

Various sections and their significance of IBR act 1923.

Sl. No.
Section No.
Used for
1.
Section-7
New boiler registration
2.
Section-8
Renewal of boiler on form VI
3.
Section-9
Provisional order on form V
4.
Section-12
Boiler alteration, modification
5.
Section-23
Penalties on illegal use of boilers












Power plant maintenance Questions & Answers

Various regulations and their significance of IBR regulation 1950.

Sl. No.
Regulations
Used for
1.
376
Preparation for boiler inspection
2.
379
Boiler hydraulic test
3.
390
Boiler open inspection
4.
391A
Boiler RLA test or NDT tests



Why do the Boilers Explode???

10-Tips to reduce LOI in Boilers

15-Emergencies in power plant operation