The Start-Up
Vent also called Start-Up Vent Line or Start-Up Vent Valve in a boiler plays a critical role during boiler start-up, shutdown, and low-load operations.
Start-up vent valve is generally
manual, motorized or pneumatic operated. Now a days all Boilers have start up
vent with motorized valve followed by pneumatic control valve.
Start-up vent line is always
tapped from main steam out let line before or after safety valves and extended
to suitable height. Start-up vent lines are equipped with silencers to reduce
sound level of super heater steam upon venting. Steam carrying capacity of the
line is 30-35% of Boiler MCR (Maximum continuous rating) or boiler capacity.
Generally, there is no flow meter
for this line.
Functions of start-up vent control valve.
Main function: Start up vent is used to
provide minimum flow to Boiler:
As
like high pressure pumps, Boilers should have minimum steam flow from Boiler
during start-ups or low load operation. And this is the main function of the start-up
vent line.
This
minimum steam flow from start-up vent is for ensuring sufficient cooling steam
is flowing through super heater coils. If NO or less steam flows through the SH
coils will lead to starvation of the coils during boiler start-ups, shut downs
and no-load operations.
There
fore operator should ensure the opening of start up vent valve during start ups
& sudden steam cut off due to process disturbance or grid failure etc.
Other functions of start-up vent valve/line
are;
1-Start up vent valve is used to
open for increasing the load on the boilers during start up. This ensure the
increase in steam temperature as the load on the Boiler increases.
2-Start up vent control valve allows
initial steam generated during boiler start-up to be vented safely
3-Start up vent valve is used to
vent out the moisture and non-condensed gases present in the super-heated steam
to ensure the right quality steam.
4-Start up vent control valve is
used to control the Boiler pressure during start-ups and shutdowns.
5- Start up vent control valve is
used to reduce the steam pressure during Turbine trip, process steam cut off or
Turbine load throw off.
6- Start up vent control valve helps
in gradual increase of steam load on boiler. This ensures uniform heating &
no stress development in pressure parts.
7-It prevents pressure surges and
water hammering in downstream pipe lines.
How to calculate Boiler safety valve discharge capacity?
8- Start up vent control valve acts
as safety valve if kept in Auto mode there by protects Boiler from over
pressure.
9- Start up vent control valve in
Auto logic operation helps in controlling main steam pressure there by avoiding
Turbine tripping on High steam pressure.
10-Even start up vent valve is
used to control the drum level during start up of safety valves floating.
When drum level rises suddenly, it
can be controlled by sudden closing of start-up vent valve.
Read more>>>Reasons for Boiler Tubes failure
In order to rise the drum level
fast, start up vent valve is used to keep open.
Start up vent typically remains
open during start ups and later can be closed gradually.
When do the Boiler start up
control valve is used??
Used during;
- Cold start up, Warm start up and Hot start up
- During planned and emergency shutdown
- During steam test (safety valve testing)
- During Turbine interlocks testing
- Start up vent is used during low load or partial load operation
- During Home load operation
- During grid failure
- During cut off of process steam