Online economiser efficiency calculator

 












Economiser efficiency is calculated as below.

ηEco. = (Economiser outlet feed water temperature Two-Economiser inlet feed water temperature Twi)  X 100 / (Economiser inlet flue gas temperature Tfi- Economiser inlet feed water temperature Twi)

Example:

Calculate the economiser effectiveness, whose feed water inlet & outlet temperatures are 150 Deg C & 220 Deg C respectively & flue gas inlet & outlet temperatures 385 deg C & 215 deg c respectively.

 Solution:

 Twi = 150 deg C

Two = 220 deg C

Tfi = 385 deg C

Tfo = 215 deg C

ηEco = (Two-Twi) X 100 / (Tfi-Twi)

ηEco = (220-150 ) X 100 / (385-150)

ηEco= 29.78%