TURBINE OIL STANDARD PARAMETERS

OIL: Servo prime 46T

Testing frequency: Every 6 months

Sl No.

Oil Property

UOM

Test Method

Acceptable limits

1

Appearance

NA

Visual

Clear/yellow Viscous liquid

2

Colour

Hazen

ASTM D1500

< 2

3

Density

Kg/m3

IS 1448-P-16:1990

820-870

4

Flash Point

0C

ATM D 93

> 180

5

Kinematic Viscosity at 40 0C

Cst

ATM D 445-17a

43-48

6

Kinematic Viscosity at 100 0C

Cst

ATM D 445-17a

>6.7

7

Viscosity index

NA

ASTM D 2270

> 98

8

RPVOT (Revolving Presure Vessel Oxidation  Stabilty Test)

Minutes

ASTM D 2272

>25% (minimum)

9

Total acid number (TAN)

mg/KOH/g

ASTM D 974

<0.2

10

Elemental analysis (Metal like Fe,Cu,Cr,Al, Ni, Sn, Si etc wear analysis)

ppm

ASTM D 5185

< 20

11

Sediments

%

IS 1866:2000

<0.01

12

Moisture content

ppm

ASTM D 6304

<1000



30-Things you mus know on steam Turbines

TRANSFORMER OIL STANDARD PARAMETERS

OIL: Transformer oil

Testing frequqency: 1 year

Sl No.

Oil Property

UOM

Test Method

Acceptable limits

1

Appearance

NA

Visual

Clear free from sediments & suspended matter

2

Density

Kg/m3

IS:1448(P:16)1990 (RA 2014)

890 max

3

Flash Point

0C

IS 1448(P:21)-2012/ATM D 93

>125

4

Pour point

0C

IS-1448 (P-10)

-6

5

Kinematic Viscosity at 27 0C

Cst

IS:1448(P:25)-1976 (RA 2007)

<27

6

Total acid number (TAN)

mg/KOH/g

S: 1448(P:2)-2007/ASTM D 974

<0.03

7

Sediments

%

IS 1866:2000

Should not be detective or <0.01

8

Moisture content

mg/kg

IS: 13567-1992 (RA 2008) /IEC-814/ASTM D 6304

<50

9

Breakdown voltage (Dielectric strength)

kv

IS: 6792-1992 (RA 2008)

40 kV

10

Tan Delta (Di–Electric Dissipation Factor) in absolute, at a Temp:900C

Degree

IS: 6262-1971 (RA 2011) 

<1

11

Resistivity (Specific Resistance) at 90 deg C

Ω-cm

IS: 6103-1971 (RA 2011) 


>35 X1012

12

Dissolved gas analysis

 

IS: 10593:2006
 &
9434-1992 
(RA 2008) or IEC 567

 

a

Methane (CH4)

ml/l

100-150 (oil life 4 to 10 years)

b

Ethylene (C2H4)

ml/l

15-200 (oil life 4 to 10 years)

c

Ethane (C2H6)

ml/l

100-150(oil life 4 to 10 years)

d

Acetylene(C2H2)

ml/l

30-50(oil life 4 to 10 years)

e

Carbon Monoxide(Co)

ml/l

400-500(oil life 4 to 10 years)

f

Carbon Dioxide (Co2)

ml/l

4000-5000(oil life 4 to 10 years)

g

Hydrogen (H2)

ml/l

200-300(oil life 4 to 10 years)

13

Interfacial Tension (IFT)

N/m

IS: 6104-1971 Ring Method (RA 2011)/ASTM D 971 

> 0.015


Questions & Answers on Power Transformer

6-Best Power plant books

Turbine oil flushing procedure

Steam Turbine SOPs

No comments:

Post a Comment

Hi all,
This article is written based on practical experience..If liked, share with others, or any suggestions leave in comment box.

What is Entropy??

  In heat engine theory, the term ENTROY plays a very vital role and leads to important results which by other methods can be obtained much ...