  1-High exhaust temperature: Vacuum drops or maintains at lower side due to high exhaust steam temperature flow into steam condenser. This high exhaust temperature is mainly due to 1-Operation of Turbine at lower loads 2-More clearance in labyrinth seals 3-Not operating exhaust hood sprays 4-More load on condenser 5-Breaking of ejector U loop 2-Low circulating cooling water flow Vacuum in condenser reduces due to inadequate cooling water flow through steam condenser. This is mainly due to; 1-Problems associated with pumps 2-Air pockets in pipe line 3-Leakages in cooling water line 4-Stuck of discharge valve of pump 3-High cooling water temperature at condenser inlet Higher cooling water temperature at condenser inlet results into reduction of vacuum due to poor heat transfer from steam to water 4-Poor heat transfer in condenser Very less or poor heat transfer in steam condenser reduces vacuum to very low level resulting into high exhaust temperature &am

Questions & Answers on Power Transformers

   

1-What do you mean by power transformer?

It is a static Electro-magnetic machine which transforms alternating current from one AC voltage to another AC voltage at same frequency & at the same apparent power (KVA).

2-What is the principle of Power transformer operation?

Power transformers work on the principle of electromagnetic induction. Which states that, EMF induced in a closed conducting circuit when the magnetic flux linking with that circuit changes in time.

3-What is the main function of a power transformer?

Generally it is used for stepping up or stepping down of Voltage to desired level

4-What are the various parts of power transformer?

General arrangement of Power Transformer


  • Casing
  • Core
  • Primary & secondary windings
  • LV & HV bushings
  • Radiators & cooling system
  • Conservator
  • Breather
  • Protection devices like Buchholz relay, relief valves, temperature sensors

5-Why does the oil conservator is placed at higher elevation?

Oil conservator is placed at a slightly higher level than that of the tank. It accommodates the contraction & expansion of oil level during lower & higher loads respectively. At higher load, oil temperature rises and hence level in the conservator rises & at lower load, oil temperature decreases & level in conservator drops down.

The above cushioning in oil level is by cushioning bag present in conservator, the air cushion in the conservator permits expansion & contraction of the oil tank without contact with moist air.

6-What is the function of breather in Transformers?

Breather is installed in a pipe from conservator. One end is connected to air cushion bag in the conservator, other end is connected to external air.

Breather is filled with dry silica jel, generally pink in colour. When oil in the conservator rises, air is let out through the breather. During low load when oil level in the conservator decreases, air is sucked into the cushion bag through breather. Silica jet absorbs the moisture & lets only dry air. Wet silica jells are blue in color.

7-What is the function of Buchholzs relay?



It is fitted in the pipe between conservator tank & main oil tank. It operates by gas during arcing or short circuits

8-What are the various cooling methods employed in Power transformers?

  • ONAN: Oil Natural & Air Natural
  • ONAF: Oil natural & Air forced
  • OFAF: Oil forced & Air forced
  • OFWF: Oil forced & water forced
  • AN: Air natural

9-What is the function of Pressure relief valve in Transformers?

It is fitted on tank to vent out the gases formed in oil & hence protects the transformer from explosion

10-What do you mean by small, medium & large transformers?

  • Small transformers: < 5 KVA
  • Medium transformers: 5 to 500 KVA
  • Large transformers :> 1 MVA

11-What do you mean by core type transformer?

In this type of transformers, winding surround the limbs of core

12-What do you mean by the Shell type transformer?

In this type of transformers, core surrounds the major portion of the windings

13-What is the relation between voltage, current and number of turns on coils in a transformer?

We have following relation:

Vp/Vs = Np/Ns = Is/Ip

Where, Vp and Vs are Voltage on primary and secondary side.

Np and Ns are No. of turns on primary and secondary coils.

IP and Is are Primary side current and secondary side current of a transformer.

14-A 10 KVA single phase 2200/220 Volts Transformer has 60 turns on secondary side, then calculate Primary current, no. of turns on coil and secondary side current.

Given that,

Vp = 2200 V

Vs 200 V

Ns 60

Transformer rating 10 KVA

We know that Vp/Vs = Np/Ns

Np 60 X 2200/220 = 600 turns

Further, KVA rating of transformer is (Vp Ip)/1000 and (Vs X Is)/1000

10 2200 Ip/1000

Therefore, current on primary side Ip 10 X 1000/2200 = 4.54 Amps

Similarly current on secondary side Is 10 1000/220 45.45 Amps

15-A Power transformer’s input voltage is 11 KV & output voltage is 110 KV,then calculate the number of turns on secondary side, if Primary side winding has 25 turns

We have

V1 / V2 = N1 / N2

11 / 110 = 25 / N2

N2 = 250 Nos

16-A power transformer input voltage is 11 KV & output voltage is 220 KV, then calculate the secondary side current if it has 2300 Amps of current on primary side?

We have

V1 / V2 = I2 / I1

11 / 220 = I2 / 2300

I2 = 115 Amps

17-What are the materials of composition of lamination cores?

Laminations are thin 0.2 to 0.3mm thick silicon sheets. These are further coated by varnish or insulation oxide.

18-Why do the laminations are made up of silicon steel sheets?

Higher the silicon content in steel sheets increases the resistivity & reduces the eddy current losses. But silicon percentage is restricted up to 3.25% max.to avoid brittleness of sheet.

19-What are the various tests carried out on Transformers?

Meggering

  • IR value measurement
  • Magnetic balance test
  • Magnetizing current test
  • Capacitor measurement
  • Ratio test
  • Vector group test
  • Induced voltage test
  • Temperature rise test
  • BDV test
  • No load current test
  • No load loss test

20-What is the significance of magnetizing current test?

  • This test is performed to locate the defects in the magnetic core structure,
  • To detect the shifting of winding, failure
  • To detect the problems in tap changers

21-What are factors which affect IR value of transformer?

  • Surface condition of the terminal bushings
  • Quality of oil
  • Quality of winding insulation
  • Temperature of oil
  • Duration of application & value of test voltage

22-What are the various protections given for power transformers?

  • Differential protection for earth faults
  • High oil temperature & high winding temperature protection
  • Over current protection
  • Over fluxing protection
  • Protection against fire
  • Protection against lightening
  • Buchholz relay for gas & arcing protection
  • Pressure relief valve

23-On what factors transformer loading depends on?

  • Transformer current
  • Winding temperature
  • Oil temperature

24-What are the effects of Transformer over loading?

Overloading results into

  • Cellulose insulation becomes mechanically weak & resulting in winding failure
  • Oil gets rapidly oxidized

25-What is the function of tap changer in Power transformers?

Tap changer is for adjusting the secondary voltage

26-What do you mean by No-load current?

The current flowing through the terminal of a winding when rated voltage is applied at rated frequency the other winding being left open circuited

27-What do you mean by no-load losses in Power transformers?

The active power absorbed when rated voltage at rated frequency is applied to the terminals of one winding, with other winding being left open circuited

28-What parameters of Transformer oil are tested yearly?

Transformer oil qualities are recommended as per IS-335-1963

  • Density
  • Kinematic Viscosity
  • Flash Point
  • Pour point
  • Neutralization Number (Acidity)
  • Sludge
  • Moisture content
  • Dissolved Gas Analysis (DGA)
  • Dielectric Dissipation test
  • Interfacial tension
  • Break down Voltage

29-What is the importance of Transformer BDV test?

BDV test is done to detect moisture, dirt & conductive particles in the oil. The BDV value should be more than 50 KV

30-Briefly explain the BDV test of transformer oil?

This test applies an AC voltage of frequency 40 to 60 Hz through two polished electrodes having diameter 12.5mm to 13 mm with oil gap around 2.5 to 4.0 mm.Rise in voltage between the electrodes is at uniform rate of 2 KV/sec.Thus voltage is increased from zero to till breakdown.

The final value will be arithmetic mean of 6 consecutive tests

 

 

Comments

Frequently visited posts

Boiler feed pumps (BFP) questions & answers for interview

Boiler feed pumps (BFP) questions & answers for interview: 1-What is the function of Boiler feed pumps (BFP) in power plant? Functions: To supply the feed water to boilers To conduct the Boiler hydraulic tests To supply the desuperheating & attemperator water required for process steam lines & boilers respectively TOP-6 BEST POWER PLANT O&M BOOKS Boiler calculations for Boiler operation engineer (BOE) exam Viva Questions & answers for preparation of BOE exam & interview  2- What are the type of prime movers (drives) used for BFPs? Prime movers: LT drive (415 V) HT drive (11 KV) Turbo drive (Steam driven) 3-What are the auxiliaries associated with BFP? BFP auxiliaries Cooling water pump & lines Lube oil system ARC valve Mechanical seal flushing system Balance leak off line & its PRV 4-What are the various pipe lines connected to BFP? Questions & Answers on AFBC Boilers Suction pipe line D

Basic things you must know about nut bolts & spanners

A Bolt is a mechanical device which has head on one end of a body and a thread on the other end designed for fastening of two parts. Bolt is inserted into holes in assembly parts, it is mated with a tapped nut. Tension is normally induced in the bolt to compress the assembly by rotating the nut. This may also be done by rotation of the bolt head. A Screw is a headed and threaded bolt used without a nut. It is inserted into an internally tapped hole and tension is induced by rotation of the screw head. A Stud is a fastener with no head but it has threads at both ends of the shank. It, like a screw, has one end those screws into a tapped hole. A nut is used on the other end to create tension. Major diameter – largest diameter of thread (D) Minor diameter – smallest diameter of thread Pitch – distance between adjacent threads.       Boiler calculations for Boiler operation engineer (BOE) exam TOP-6 BEST POWER PLANT O&M BOOKS Types of nut bolts & Washer

Calculation of heat rate & efficiency of the power plant

Heat rate  is the amount of energy used by an electrical generator/power plant to generate one kilo Watt-hour (kWh) of electricity Heat rate (HR) = Heat input / Power generation =Kcal / Kwh Boiler calculations for Boiler operation engineer (BOE) exam Viva Questions & answers for preparation of BOE exam & interview Total heat input: The chemical energy available in the fuel (coal, biomass, oil, gas etc) is converted into heat energy in Boilers, this process is called as oxidation. The heat available in the fuel is measured in terms of Kcal/kg, KJ/kg or BTU units. The part of this fuel is used as useful heat and rest is lost as dry flue gas loss, moisture loss, un  burnt loss, radiation/convection losses etc.Based on Boiler efficiency this heat energy from the fuel is utilised, generally fuel heat utilisation is in the range of 60 to 90%. This heat generated in the boilers due to oxidation of fuel is used to generate high pressure & temperature steam. Thus genera

STEAM CONDENSER,VACUUM AND CALCULATIONS

A steam condenser is device or an appliance in which steam condenses and heat released by steam is absorbed by water. Heat is basically shell & tube type heat exchanger, where cooling water passes through tubes & steam condenses in shell. The functions of the condensers are: It condenses the steam exhausted from Turbine last stage Increase the thermal efficiency of the plant reducing the exhaust pressure and thereby reducing the exhaust temperature It maintains a very low back pressure on the exhaust side of the Turbine Supplies feed water to Boiler through deaerator TOP-6 BEST POWER PLANT O&M BOOKS Condenser related components: Hot well Cooling water inlet & outlet system Cooling tower Support springs or expansion neck Air Ejector system Condensate extraction system Cooling water tubes & tube sheet Vacuum breaker valve Safety valve or rapture disc Water box Air & water vent lines Types of steam condensers: Surface Co

22-Most likely Question Answer Guide for Boilers troubleshooting

TOP-6 BEST POWER PLANT O&M BOOKS 1.What are the emergencies that are expected to happen in boiler operation? Emergencies that can happen in boilers operation are: Boilers tubes leakage Failure of feed water control station Unbalanced draft in furnace Furnace explosion Blow down valve failure Feed water pumps failure Secondary combustion in super heaters and ESP Also read 16-Perfect reasons for increasing the fuel consumption of Boilers 2.List out the potential reasons for boiler tubes failure. Reasons for boiler tubes failure: Failure due to overheating Failure due to internal scales Failure due to aging Failure due to uneven expansion Failure due to ash and flue gas erosion Failure due to material defects Failure due to internal and external tube corrosion Improper or effected circulation due to opening/passing of low point drains 3.List down the sequential action taken after boiler tube leakage to restore the boiler. Following activities ar

Questions answers & calculation on Boiler draught & Chimney

1-What do you mean by the term draught? It is the pressure difference, which causes flow of gases to take places. 2-What is the function of draught in Boiler? To supply the combustion air required for proper combustion To evacuate the combustion products from the furnace or combustion chamber To evacuate the combustion products to the atmosphere So draught is the pressure difference between the inside the boiler and outside air. Inside the boiler pressure is due to combustion products (Flue gas) & outside pressure is due to fresh atmospheric air. 3-What are the different types of draughts used in power plant boilers? There are mainly two types of draughts. Natural draught & artificial draught Natural draught is generally obtained by Chimney Artificial draughts have main two types Steam jet: It is again classified into Induced & forced draught Mechanical draught: This is classified into Induced draught, forced draught & Natural draught

Boiler calculations for Boiler operation Engineer Exam (BOE)

  1-Oxygen percentage in Boiler outlet flue gas is 4.9%, then what will be the percentage of excess air? We have excess air EA = O2 X 100 / (21-O2)                                    EA = 4.7 X 100 / (20-4.7)                                    EA = 30.71% 2-Calculate the Oxygen level (O2) in flue gas, if excess air is 25% We have Excess air EA = O2 X 100 / (21-O2)                                    25 = O2 X 100 / (21-O2)                                    O2 = 4.2% 3-A Boiler’s combustion system requires 5.5 kg of air for burning 1 kg of fuel, then calculate the total air required for complete combustion if its flue gas has 4.1% of O2 We have, Total air = (1 + EA/100) X Theoretical air EA = O2 X 100 / (21-O2) EA = 4.1 X 100 / (20-4.1) = 25.78% Therefore Total air = (1 + 25.78/100) X 5.5 = 6.92 kg of air per kg of fuel burnt 4-A Coal fired boiler having total heating surface area 5200 M2 produces 18 kg of steam per square meter per hour of heating surface, then calculate the Boiler cap
close